Skip to content
← All transformers

SBP‑150‑XFMR‑ND‑ISO

150 kVA Isolation Transformer

150 kVA mobile isolation transformer without integrated distribution. Switchable 480/600 V primary, 120/208 V secondary, 400A cam lock in and out.

Rating150 kVA
Primary480/600 V switchable
Secondary120/208 V Y
Full-load secondary416 A @ 208 V

Features

  • Wide range of options and accessories available
  • Simple access for maintenance and operations
  • Weatherproof enclosure, NEMA 3R compliant
  • Safety guards for all electrical connections
  • All parts powder coated, galvanized or aluminum
  • Single point lifting bail system, engineered and rated
  • UL 489-rated built-in adjustable breakers for transformer protection
  • Switchable 480/600 V primary with lockable selector switch

Transformer

  • 3-phase isolation transformer, aluminum windings, self-cooled (ANN/AN)
  • Efficiency: U.S. DOE 2016 (10 CFR Part 431); Canada NRCan 2019 (SOR/2018-201, Amd. 14) and Ontario Reg. 404/12
  • Sound level meets NEMA ST-20
  • CSA Certified – File LR34493 (5 kV max, 900 kVA max)
  • UL Listed – File E108255 (600 V max, 750 kVA max)
  • 220 °C / 428 °F insulation rating

Unit specifications

Electrical
kVA rating150
Transformer typeIsolation
Primary voltage480/600 V switchable
Secondary voltage120/208 V Y
Full-load primary amps @ 480 V 3Ø180 A
Full-load primary amps @ 600 V 3Ø144 A
Full-load secondary amps @ 208 V 3Ø416 A
Efficiency (35% load, 75 °C)98.83 %
Impedance3.5% – 5.5%
Primary taps available480V, 570V, 600V, 630V
Average sound level50 dB
CoolingANN/AN self-cooled
Insulation rating220 °C
Connections and distribution
Primary inlet2 × 400A Cam Lock (L1, L2, L3, GND); optional blank gland plate for hard wire
Secondary outlet2 × 400A Cam Lock (L1, L2, L3, N, GND); optional blank gland plate for hard wire
Protection
Primary protection400 A MCCB, 0.8 adjustable, UL 489
Secondary protection500 A MCCB, 0.8 adjustable, UL 489
Physical
Dimensions (L × W × H)41 × 41 × 54 in
Enclosure typeType 3R Outdoor
LiftingSingle point bail
Compliance and approvals
StandardsSPE-1000, UL 1640 compliant design, CSA C22.2 No. 5, UL 489, IEC/EN 60947-2, CE compliant

The SBP Transformer range without integrated power distribution is currently in development and may be subject to change. Final specifications will be provided for customer approval prior to manufacturing.

2026-09 Rev A · reviewed 2026-09-06 · ©2026 Eco Power Equipment Ltd. Specifications subject to change without notice.