Skip to content
← All transformers

SBP‑300‑XFMR

300 kVA Transformer Power Module

300 kVA mobile isolation transformer with integrated power distribution. Switchable 480/600 V primary, 120/208 V secondary, configurable with the Eco Power common gland system.

Rating300 kVA
Primary480/600 V switchable
Secondary120/208 V Y
Full-load secondary833 A @ 208 V

Features

  • Prototype and production tested design
  • Wide range of options and accessories available
  • Simple access for maintenance and operations
  • Weatherproof enclosure, NEMA 3R compliant
  • Safety guards for all electrical connections
  • Tool-less lockable latches standard
  • All parts powder coated, galvanized or aluminum
  • Single point lifting bail system, engineered and rated
  • All components listed; UL 489-rated transformer protection built into the assembly
  • Switchable 480/600 V primary with lockable selector switch – connect between 480 V generators and 600 V utilities without changing your power distribution
  • Power distribution customizable with the Eco Power Equipment gland system

Transformer

  • 3-phase isolation transformer, aluminum windings, self-cooled (ANN/AN)
  • Efficiency: U.S. DOE 2016 (10 CFR Part 431); Canada NRCan 2019 (SOR/2018-201, Amd. 14) and Ontario Reg. 404/12
  • Sound level meets NEMA ST-20
  • CSA Certified – File LR34493 (5 kV max, 900 kVA max)
  • UL Listed – File E108255 (600 V max, 750 kVA max)
  • 220 °C / 428 °F insulation rating

Unit specifications

Electrical
kVA rating300
Transformer typeIsolation
Primary voltage480/600 V switchable
Secondary voltage120/208 V Y
Full-load primary amps @ 480 V 3Ø361 A
Full-load primary amps @ 600 V 3Ø289 A
Full-load secondary amps @ 208 V 3Ø833 A
Efficiency (35% load, 75 °C)99.02 %
Impedance4% – 6%
Primary taps available480V, 570V, 585V, 600V, 615V, 630V
Average sound level55 dB
CoolingANN/AN self-cooled
Insulation rating220 °C
Connections and distribution
Primary inlet2 × 400A Cam Lock or hard wire
Primary splitterYes
Secondary distributionI-Line
Panelboard1200 A Square D
Secondary breaker typeBD, BG, BJ, BK, QB, QD, QG, QJ
Circuit capacity36
Gland capacity8
Protection
Primary protection800 A MCCB, 0.8 adjustable, UL 489
Secondary protection1200 A MCCB, 0.8 adjustable, UL 489
Physical
Dimensions (L × W × H)72 × 47 × 68 in
Weight3500 lbs
Enclosure typeType 3R Outdoor
LiftingSingle point bail
Compliance and approvals
StandardsSPE-1000, UL 1640 compliant design, CSA C22.2 No. 5, UL 489, IEC/EN 60947-2, CE compliant

2026-09 Rev A · reviewed 2026-09-06 · ©2026 Eco Power Equipment Ltd. Specifications subject to change without notice.