Skip to content
← Automatic Transfer Switches

SBP‑1600‑ATS

SBP-1600-ATS Mobile Automatic Transfer Switch, 1600 A

Mobile 1600 A air-circuit-breaker automatic transfer switch, selectable 120/208 to 347/600 V, ComAp controller, arctic-rated NEMA 3R aluminum enclosure.
Rated current1600 A · 3Ø
Voltage120/208 V to 347/600 V selectable
SwitchingACB · 85 kA withstand · NEMA 3R
Camlock5 × 400 A per phase

Features

  • Heavy-duty air circuit breaker (ACB) based design
  • Switchable voltage design: 120/208 V, 120/240 V, 277/480 V, 347/600 V with lockable selector switch
  • Integrated control-panel heating system, arctic-rated design
  • Advanced control system for application flexibility
  • Amperage monitoring and data logging
  • Fully programmable controller for application integration
  • Display of all critical ATS measures
  • Remote cellular or satellite telematics ready
  • Integrated battery backup system with one-week life
  • Battery charging port with battery disconnect
  • Single-point lifting bail, engineered and rated
  • Highly portable enclosure with fork pockets, castor ready
  • Rugged base frame and enclosure for mobile applications
  • Aluminum enclosure for long-term wear
  • Lockable latches standard, key or external lock
  • Stackable frame
  • Simple access for maintenance and operations
  • Camlock source and load connections on Eco Power standard cam panels, paralleled per phase
  • Wide range of options and accessories available

Application notes

  • Camlock connections are paralleled per phase so the unit holds full rating at high ambient: each 400 A cam is derated to 320 A in heat
  • Separate ground connection: 5 x 400 A male camlock
  • Weight is approximate
  • Continuous operation at 100% of rated current
  • Shunt trip and closing release: 110 to 130 V AC control voltage, under 50 ms operating time
  • Integrated 25 kVA transformer feeds the shore power package

Unit specifications

Ratings
Rated current1600 A
PhasesThree-phase (3Ø)
Maximum system voltage600 V AC
Selectable voltages
  • 120/208 V
  • 120/240 V
  • 277/480 V
  • 347/600 V
Lockable selector switch.
Operating temperature-40 to +40 °C (-40 to 104 °F)
Switching
Switching deviceAir circuit breaker (ACB)
Withstand rating85 kA @ 847 V
Device standardsUL 1066, CSA C22.2 No. 268, ANSI C37.13, ANSI C37.16, ANSI C37.17, ANSI C37.50
Switching device ratings
  • Rated operational current 1600 A, continuous at 1.0
  • Temperature derate: 1.00 to 55 °C, 0.95 at 55 °C, 0.92 at 60 °C, 0.88 at 65 °C, 0.85 at 70 °C
  • Altitude derate, voltage: 1.00x to 200 m, 0.95x at 2600 m, 0.80x at 3900 m, 0.70x at 4900 m
  • Altitude derate, current: 1.00x to 200 m, 0.99x at 2600 m, 0.96x at 3900 m, 0.94x at 4900 m
Controls and protection
ControllerComAp
Controller features
  • ComAp ATS controller for standby and prime-power applications
  • Mains-to-mains, mains-to-gen or gen-to-gen application
  • All-in-one PC tool for configuration, monitoring and control, local or remote
  • PLC editor for user-configurable functions
  • Real-time clock with battery backup, full calendar
  • Detailed history log, up to 350 records
  • Current measurement in all phases, true RMS
  • English and French languages
  • Active SMS and email alerts (with 4G option)
  • Controller country of origin: Czech Republic
Protections
  • Reverse power
  • Voltage-dependent overcurrent
  • Overcurrent
  • Undervoltage
  • Overvoltage
  • Under frequency
  • Overload (real power)
  • Current unbalance
  • Voltage unbalance / negative-sequence voltage
  • Breaker or contactor failure
  • Aux battery undervoltage
  • Aux overvoltage
  • Annunciator
  • Auto selective control / transfer
Connections
Camlock connections5 × 400 A per phase, paralleled
Installed cam capacity per phase2000 A nominal · 1600 A at the 320 A/cam high-ambient derate
Shore power
Shore power package
  • 2 x 120 V 20 A GFCI duplex
  • 2 x 120/240 V 50 A twist-lock CS6369
  • With integrated 25 kva transformer
Physical
Weight1,490 lb
Enclosure typeNEMA 3R
LiftingSingle-point lifting bail, engineered and rated; fork pockets; castor ready
Compliance and approvals
StandardsSPE-1000, CSA C22.2 No. 178.1, UL 1008

We work diligently to ensure all product information is accurate at the time of publication. Specifications, features, dimensions, and availability are subject to change without notice. Images are for illustration purposes and may show optional equipment or configurations that differ from the product supplied. Published information is provided for general reference and does not constitute a warranty or contractual commitment. Confirm all critical specifications and application requirements with us in writing before ordering. Final supply is governed by the accepted order and applicable terms of sale. To the extent permitted by law, we disclaim liability for errors, omissions, or reliance on outdated information. Nothing in this notice overrides expressly agreed contractual obligations or applicable statutory rights.

· ©2026 Eco Power Equipment Ltd.