CIPR‑120WT
CIPR-120W · Trailer

Features
- Prototype and production tested design
- Weatherproof enclosure with 110% fluid containment
- Safety guards on all electrical connections and moving parts
- Lockable latches, key or external lock
- Engineered vibration dampening
- Single-point engineered and rated lifting bail
- Rugged base frame and enclosure for mobile applications
- Internal silencer and catalytic converters
- All parts powder coated or galvanized
- Integrated power distribution
- Display of all critical genset measures
Rating basis and notes
Ratings at ISO 8528 reference conditions (100 kPa, 25 °C, 30% RH). Site conditions may require derating — consult the factory.Unit specifications
| Ratings (60 Hz, ISO 8528) | |
|---|---|
| Prime power — natural gas | 97 kW / 108 kVA |
| Standby power — natural gas | 108 kW / 120 kVA |
| Standard voltage | 277/480 V 3Ø |
| Voltages available |
Field-switchable voltage system fitted as standard. |
| Phase / frequency | 3Ø · 60 Hz (50 Hz capable) |
| Power factor | 0.8 |
| Full-load current (prime, NG) | 337 A @ 208 V · 292 A @ 240 V · 146 A @ 480 V · 117 A @ 600 V |
| Fuel | |
| Fuels | Natural gas, Vapour propane |
| Standard configuration | Natural gas or vapour propane |
| Fuel specification | Propane HD5 (≥90% C3H8, ≤5% C3H6); utility natural gas |
| Engine | |
| Make / model | PSI 10L NA |
| Cylinders / displacement | I6, inline · 9,730 cc |
| Air intake | Naturally aspirated |
| Engine power | 178 / 160 hp prime (LP / NG) |
| Speed | 1800 rpm |
| Starting system | Electric, 24 V |
| Battery | 2 × 1000 CCA |
| Emissions | Environment Canada / US EPA |
| Cooling | Mechanical fan |
| Lube oil capacity | 30 L / 7.9 US gal |
| Oil type | API SL or higher; SAE 10W-30 |
| Coolant capacity | 50 L / 13.2 US gal |
| Service interval | 750 h |
| Alternator | |
| Make / model | Mecc Alte ECP34-2M4 |
| Regulator | DSR |
| Poles / speed | 4 pole · 1800 rpm |
| Voltage regulation | ±1% |
| Continuous rating (125/40 °C) | 162 kVA |
| Standby rating (150/40 °C) | 178 kVA |
| Efficiency @ 100% load | 92.9 % |
| Harmonic distortion | <5% |
| Protection / insulation | IP23 / Class H |
| Compliance | CSA C22.2-100, NEMA MG1-32, IEC 34 |
| Controls and distribution | |
| Controller | DEIF AGC 150 |
| Controller features |
|
| Protections |
|
| Telematics | Eco Connect (October 2026 Onwards) |
| Emergency stop | Externally accessible |
| Standard power distribution |
|
| Trailer | |
| Axles | torsion |
| Lighting | DOT / Transport Canada light kit |
| Physical | |
| Genset weight | 6,950 lb |
| Enclosure type | NEMA 3R |
| Lifting | Single point bail |
| Compliance and approvals | |
| Standards | ETL; alternator CSA C22.2-100, NEMA MG1-32, IEC 34 |
Trailer specifications (dimensions, weights, GVWR, axle ratings, hitch, tongue weight, tires, compliance) under Engineering review.
We work diligently to ensure all product information is accurate at the time of publication. Specifications, features, dimensions, and availability are subject to change without notice. Images are for illustration purposes and may show optional equipment or configurations that differ from the product supplied. Published information is provided for general reference and does not constitute a warranty or contractual commitment. Confirm all critical specifications and application requirements with us in writing before ordering. Final supply is governed by the accepted order and applicable terms of sale. To the extent permitted by law, we disclaim liability for errors, omissions, or reliance on outdated information. Nothing in this notice overrides expressly agreed contractual obligations or applicable statutory rights.