CIPR‑50KS
CIPR-50K · Skid

Features
- Prototype and production tested design
- Weatherproof enclosure with 110% fluid containment
- Safety guards on all electrical connections and moving parts
- Lockable latches, key or external lock
- Engineered vibration dampening
- Single-point engineered and rated lifting bail
- Rugged base frame and enclosure for mobile applications
- Internal silencer and catalytic converters
- All parts powder coated or galvanized
- Integrated power distribution
- Display of all critical genset measures
Rating basis and notes
Ratings at ISO 8528 reference conditions (100 kPa, 25 °C, 30% RH). Site conditions may require derating — consult the factory.Unit specifications
| Ratings (60 Hz, ISO 8528) | |
|---|---|
| Prime power — natural gas | 40 kW / 50 kVA |
| Standby power — natural gas | 42 kW / 52.5 kVA |
| Prime power — propane | 45 kW / 56.25 kVA |
| Standby power — propane | 47 kW / 58.75 kVA |
| Standard voltage | 120/208 V 3Ø |
| Voltages available |
|
| Phase / frequency | 3Ø · 60 Hz (50 Hz capable) |
| Power factor | 0.8 |
| Full-load current (prime, NG) | 139 A @ 208 V · 120 A @ 240 V · 60 A @ 480 V · 48 A @ 600 V |
| Fuel | |
| Fuels | Natural gas, Vapour propane |
| Standard configuration | Natural gas or vapour propane |
| Fuel specification | Propane HD5 (≥90% C3H8, ≤5% C3H6); utility natural gas |
| Engine | |
| Make / model | Kubota WG3800 |
| Cylinders / displacement | I4, inline · 3,769 cc |
| Air intake | Naturally aspirated |
| Engine power | 77.5 bhp prime (NG) |
| Speed | 1800 rpm |
| Starting system | Electric, 12 V |
| Emissions | Environment Canada / US EPA |
| Cooling | Mechanical fan |
| Lube oil capacity | 12.2 L / 3.2 US gal |
| Service interval | 750 h |
| Alternator | |
| Make / model | Mecc Alte ECP32-1M |
| Regulator | DSR |
| Poles / speed | 4 pole · 1800 rpm |
| Voltage regulation | ±1% |
| Continuous rating (125/40 °C) | 60 kVA |
| Standby rating (150/40 °C) | 66 kVA |
| Efficiency @ 100% load | 90 % |
| Harmonic distortion | <5% |
| Protection / insulation | IP23 / Class H |
| Compliance | CSA C22.2-100, NEMA MG1-32, IEC 34 |
| Controls and distribution | |
| Controller | ComAp InteliNano AMF 5 |
| Controller features |
|
| Protections |
|
| Telematics | Eco Connect (October 2026 Onwards) |
| Emergency stop | Externally accessible |
| Standard power distribution |
|
| Physical | |
| Weight | 3375 lbs |
| Enclosure type | NEMA 3R |
| Lifting | Single point bail |
| Compliance and approvals | |
| Standards | ETL; alternator CSA C22.2-100, NEMA MG1-32, IEC 34 |
Weight, power factor and alternator data to be confirmed by Engineering.
We work diligently to ensure all product information is accurate at the time of publication. Specifications, features, dimensions, and availability are subject to change without notice. Images are for illustration purposes and may show optional equipment or configurations that differ from the product supplied. Published information is provided for general reference and does not constitute a warranty or contractual commitment. Confirm all critical specifications and application requirements with us in writing before ordering. Final supply is governed by the accepted order and applicable terms of sale. To the extent permitted by law, we disclaim liability for errors, omissions, or reliance on outdated information. Nothing in this notice overrides expressly agreed contractual obligations or applicable statutory rights.