Skip to content
← All models

SBP‑300‑XFMR

300 kVA Transformer Power Module

300 kVA mobile isolation transformer with integrated power distribution. Switchable 480/600 V primary, 120/208 V secondary, configurable with the Eco Power common gland system.

Rating300 kVA
Primary480/600 V switchable
Secondary120/208 V Y
Full-load secondary833 A @ 208 V

Features

  • Prototype and production tested design
  • Wide range of options and accessories available
  • Simple access for maintenance and operations
  • Weatherproof enclosure, NEMA 3R compliant
  • Safety guards for all electrical connections
  • Tool-less lockable latches standard
  • All parts powder coated, galvanized or aluminum
  • Single point lifting bail system, engineered and rated
  • All components listed; UL 489-rated transformer protection built into the assembly
  • Switchable 480/600 V primary with lockable selector switch – connect between 480 V generators and 600 V utilities without changing your power distribution
  • Power distribution customizable with the Eco Power Equipment gland system

Transformer

  • 3-phase isolation transformer, aluminum windings, self-cooled (ANN/AN)
  • Efficiency: U.S. DOE 2016 (10 CFR Part 431); Canada NRCan 2019 (SOR/2018-201, Amd. 14) and Ontario Reg. 404/12
  • Sound level meets NEMA ST-20
  • CSA Certified – File LR34493 (5 kV max, 900 kVA max)
  • UL Listed – File E108255 (600 V max, 750 kVA max)
  • 220 °C / 428 °F insulation rating

Unit specifications

Electrical
kVA rating300
Transformer typeIsolation
Primary voltage480/600 V switchable
Secondary voltage120/208 V Y
Full-load primary amps @ 480 V 3Ø361 A
Full-load primary amps @ 600 V 3Ø289 A
Full-load secondary amps @ 208 V 3Ø833 A
Efficiency (35% load, 75 °C)99.02 %
Impedance4% – 6%
Primary taps available480V, 570V, 585V, 600V, 615V, 630V
Average sound level55 dB
CoolingANN/AN self-cooled
Insulation rating220 °C
Connections and distribution
Primary inlet2 × 400A Cam Lock or hard wire
Primary splitterYes
Secondary distributionI-Line
Panelboard1200 A Square D
Secondary breaker typeBD, BG, BJ, BK, QB, QD, QG, QJ
Circuit capacity36
Gland capacity8
Protection
Primary protection800 A MCCB, 0.8 adjustable, UL 489
Secondary protection1200 A MCCB, 0.8 adjustable, UL 489
Physical
Dimensions (L × W × H)72 × 47 × 68 in
Weight3500 lbs
Enclosure typeType 3R Outdoor
LiftingSingle point bail
Compliance and approvals
StandardsSPE-1000, UL 1640 compliant design, CSA C22.2 No. 5, UL 489, IEC/EN 60947-2, CE compliant

We work diligently to ensure all product information is accurate at the time of publication. Specifications, features, dimensions, and availability are subject to change without notice. Images are for illustration purposes and may show optional equipment or configurations that differ from the product supplied. Published information is provided for general reference and does not constitute a warranty or contractual commitment. Confirm all critical specifications and application requirements with us in writing before ordering. Final supply is governed by the accepted order and applicable terms of sale. To the extent permitted by law, we disclaim liability for errors, omissions, or reliance on outdated information. Nothing in this notice overrides expressly agreed contractual obligations or applicable statutory rights.

We work diligently to ensure all product information is accurate at the time of publication. Specifications, features, dimensions, and availability are subject to change without notice. Images are for illustration purposes and may show optional equipment or configurations that differ from the product supplied. Published information is provided for general reference and does not constitute a warranty or contractual commitment. Confirm all critical specifications and application requirements with us in writing before ordering. Final supply is governed by the accepted order and applicable terms of sale. To the extent permitted by law, we disclaim liability for errors, omissions, or reliance on outdated information. Nothing in this notice overrides expressly agreed contractual obligations or applicable statutory rights.