Skip to content
← All models

SBP‑75‑XFMR‑ND‑ISO

75 kVA Isolation Transformer

75 kVA mobile isolation transformer without integrated distribution, featuring 400 A cam-lock input and output connections. A four-position selector switch provides 480 V or 600 V to 120/208 V step-down operation, plus two reverse-feed settings for 208 V to 480 V or 600 V step-up operation. The reverse-feed settings disconnect the neutral-to-ground bond.

Rating75 kVA
Primary480/600 V switchable
Secondary120/208 V Y
Full-load secondary208 A @ 208 V

Features

  • Wide range of options and accessories available
  • Simple access for maintenance and operations
  • Weatherproof enclosure, NEMA 3R compliant
  • Safety guards for all electrical connections
  • All parts powder coated, galvanized or aluminum
  • Single point lifting bail system, engineered and rated
  • UL 489-rated built-in adjustable breakers for transformer protection
  • Switchable 480/600 V primary with lockable selector switch

Transformer

  • 3-phase isolation transformer, aluminum windings, self-cooled (ANN/AN)
  • Efficiency: U.S. DOE 2016 (10 CFR Part 431); Canada NRCan 2019 (SOR/2018-201, Amd. 14) and Ontario Reg. 404/12
  • Sound level meets NEMA ST-20
  • CSA Certified – File LR34493 (5 kV max, 900 kVA max)
  • UL Listed – File E108255 (600 V max, 750 kVA max)
  • 220 °C / 428 °F insulation rating

Unit specifications

Electrical
kVA rating75
Transformer typeIsolation
Primary voltage480/600 V switchable
Secondary voltage120/208 V Y
Full-load primary amps @ 480 V 3Ø90 A
Full-load primary amps @ 600 V 3Ø72 A
Full-load secondary amps @ 208 V 3Ø208 A
Efficiency (35% load, 75 °C)98.6 %
Impedance3.5% – 5.5%
Primary taps available480V, 570V, 600V, 630V
Average sound level50 dB
CoolingANN/AN self-cooled
Insulation rating220 °C
Connections and distribution
Primary inlet400A Cam Lock (L1, L2, L3, GND); optional blank gland plate for hard wire
Secondary outlet400A Cam Lock (L1, L2, L3, N, GND); optional blank gland plate for hard wire
Protection
Primary protection250 A MCCB, 0.8 adjustable, UL 489
Secondary protection250 A MCCB, 0.8 adjustable, UL 489
Physical
Dimensions (L × W × H)36 × 36 × 41 in
Enclosure typeType 3R Outdoor
LiftingSingle point bail
Compliance and approvals
StandardsSPE-1000, UL 1640 compliant design, CSA C22.2 No. 5, UL 489, IEC/EN 60947-2, CE compliant

We work diligently to ensure all product information is accurate at the time of publication. Specifications, features, dimensions, and availability are subject to change without notice. Images are for illustration purposes and may show optional equipment or configurations that differ from the product supplied. Published information is provided for general reference and does not constitute a warranty or contractual commitment. Confirm all critical specifications and application requirements with us in writing before ordering. Final supply is governed by the accepted order and applicable terms of sale. To the extent permitted by law, we disclaim liability for errors, omissions, or reliance on outdated information. Nothing in this notice overrides expressly agreed contractual obligations or applicable statutory rights.

We work diligently to ensure all product information is accurate at the time of publication. Specifications, features, dimensions, and availability are subject to change without notice. Images are for illustration purposes and may show optional equipment or configurations that differ from the product supplied. Published information is provided for general reference and does not constitute a warranty or contractual commitment. Confirm all critical specifications and application requirements with us in writing before ordering. Final supply is governed by the accepted order and applicable terms of sale. To the extent permitted by law, we disclaim liability for errors, omissions, or reliance on outdated information. Nothing in this notice overrides expressly agreed contractual obligations or applicable statutory rights.

2026-09 Rev A · reviewed 2026-09-06 · ©2026 Eco Power Equipment Ltd.